9
Compool Cp3810
System Power
System Power provides power to the transformer.
• To wire System Power
1. At the Sub-panel, install a circuit breaker for System Power. The system draws less than 1
amp. Do not use a GFCI circuit breaker.
2. Run appropriate wires from the circuit breaker to the System Power terminal block.
3. For a 115 volt connection, connect to terminals 2 and 3.
4. For a 230 volt connection, connect to terminals 1 and 3.
Caution
Incorrect wiring will cause permanent damage to the transformer.
Lx3810
SUB-PANEL
Filter
Pump
Heater
6
5
4
3
2
1
P
Solar
Auto
Service
IMPORTANT: Switch back to
Auto after servicing equipment.
Water Sensor
Solar Sensor
Sensor
Status
Auto
▲
▲
▲
▲
Auto
Service
Press Filter key 2 times quickly.
Filter Pump On:
Press
Filter key 3 times quickly.
Filter Pump Off:
To cancel:
The 3-hour override can be
cancelled by switching to
Service, and then back to Auto.
Make sure the Auto/Service
key is in the Auto position.
Override Verification:
The Auto lamp will blink
during the 3-Hour Override.
Instructions:
When adding chemicals, the filter
pump can be set to stay on for three
hours -or- stay off for three hours.
This overrides the programming of
the Cp3810 indoor controller on a
one-time basis. The same procedure
can be used on the other equipment
keys 1-6.
3 Hour Filter Override
P
P
B
Freeze Sensor
Lamp ON indicates problem with the
sensor or wires leading to sensor.
Check connections and replace sensor
if necessary.
▲
▲
B.wash
Comments to this Manuals